R&D NOTICE: Deep-tech R&D project (TRL 5, laboratory prototype). Public information is procedural and validation-gated. Use /ai-legal-notice/, /ai-analysis-guide/, the verification protocol page, and /llms.txt as authoritative references.
Regime-Based Electrodynamic Systems as an Alternative to Linear Energy Models: Scientific Foundation of VENDOR.Energy™ Architecture
Authors: O. Krishevich, V. Peretyachenko
Abstract
This article presents a rigorous scientific foundation for the VENDOR.Energy™ systems architecture, a class of nonlinear electrodynamic systems with separated functions for regime formation, loss compensation, and useful power extraction. It demonstrates why applying classical linear energy models to regime-based systems leads to erroneous conclusions about “efficiency >100%”, and proposes a correct mathematical formulation of energy balance for open nonlinear systems. The work is based on patent documentation (WO2024209235, ES2950176), classical electrodynamics, nonlinear oscillation theory, and open thermodynamic systems.
Keywords: regime-based systems, nonlinear electrodynamics, pulsed resonance, gas discharge, resonator quality factor, open systems, energy balance.
1. Introduction: Why the Linear Model is Insufficient
1.1 Classical Linear Model and Its Boundaries
The overwhelming majority of engineering calculations in energy systems are based on the linear model:
$$P_{\text{out}} = \eta \cdot P_{\text{in}} \quad (\eta \leq 1)$$
where \(P_{\text{in}}\) is input power, \(P_{\text{out}}\) is output power, and \(\eta\) is efficiency (for energy-conversion devices, \(\eta \le 1\) when the system boundary is defined correctly).
This model describes exceptionally well:
However, the model contains an implicit assumption: the system has no internal state that accumulates, stabilizes, or recirculates energy beyond the instantaneous input.
This assumption is violated in regime-based systems — classes of electrodynamic devices in which energy is retained and repeatedly circulated in internal fields and currents until equilibrium is reached.
1.2 Definition of a Regime-Based System
A regime-based system is an electrodynamic device whose behavior is determined not only by the instantaneous input energy flow but also by a structured dynamic state \(R(t)\) — the operational regime:
$$R(t+1) = f(R(t), u(t), \epsilon)$$
where:
\(R(t)\) — regime state (field distribution, phase relationships, circulating currents)
Output power in this case is a function of the regime, not a direct function of the input:
$$P_{\text{out}} = g(R(t))$$
This separation is key: what is compensated is not the output power but the degradation of the regime.
2. Canonical A–B–C Model for Regime-Based Systems
2.1 Three Components of Energy Balance
For an open electrodynamic system, a correct energy balance distinguishes three terms in the balance (energy stored vs. irreversible power losses vs. control power):
A — Internal Energy Turnover
$$A(t) = \sum_i U_i(t) \cdot n_i(t)$$
where \(U_i(t)\) is energy stored in the \(i\)-th reactive component (capacitor field, inductor flux), and \(n_i(t)\) is the effective number of circulation cycles before dissipation.
Physically, this is the multiple circulation of energy in electric and magnetic fields of the active circuit:
Energy transitions from electric field to magnetic field and back
Each cycle is determined by resonant frequency and quality factor
Internal circulation (reactive energy turnover) can be much larger than the net input power, which is a standard property of high-Q resonant systems
\(P_{\text{dielectric}}\) — dielectric losses (in insulation, air)
\(P_{\text{radiation}}\) — electromagnetic energy radiation
\(P_{\text{discharge}}\) — losses in gas discharge (ionization, heat, chemistry)
Important: these losses are internal to the system and determine the required compensation, but are not equal to output power.
C — External Loss-Compensation Power
$$P_{\text{control}}(t) \approx B_{\text{maint}}(t)$$
In steady state:
$$P_{\text{control,steady}} \approx B_{\text{maint,steady}}$$
where \(B_{\text{maint}}(t)\) denotes the subset of regime losses that must be compensated to keep the regime stable (e.g., core ohmic/dielectric/discharge losses), as distinct from load-dependent extraction losses reflected through the effective loaded quality factor.
Critical property: \(P_{\text{control}} \neq P_{\text{out}}\)
Output power is extracted from turnover \(A\) through a separate channel (extraction circuit), and its magnitude depends on extraction architecture and regime stability boundaries, but not directly on \(P_{\text{control}}\).
2.2 Energy Balance for an Open System
The complete energy balance can be written as:
$$\frac{dE_{\text{total}}}{dt} = P_{\text{in,total}} – B(t) – P_{\text{out}}$$
Here \(B(t)\) aggregates all irreversible power leaving the chosen system boundary (heat, radiation, chemical processes in discharge, etc.).
where \(P_{\text{in,total}}\) is the total measured power entering the system boundary (all electrical inputs).
In parallel, we distinguish the control/maintenance channel:
$$P_{\text{control}} \approx B_{\text{maint}}(t)$$
i.e., the power required to keep the operating regime stable is primarily the power that compensates irreversible maintenance losses — not necessarily the full delivered output.
In steady state \(\frac{dE_{\text{total}}}{dt} = 0\):
$$P_{\text{in,total}} = B(t) + P_{\text{out}}$$
That is: total input covers the sum of losses and useful extraction.
This fundamentally differs from the linear model \(P_{\text{out}} = \eta \cdot P_{\text{in}}\), where external input is directly proportional to output.
3. Physical Foundations of Regime Formation in VENDOR: Gas Discharge and Resonance
3.1 Pulsed Pumping and LC Resonance
The active circuit of the VENDOR system is built on the principle of pulsed pumping of a reactive structure. At its core is an effective series or parallel combination of inductance \(L\) and capacitance \(C\):
$$\omega_0 = \frac{1}{\sqrt{LC}} \quad \text{(resonant frequency)}$$
$$Q = \frac{\omega_0 L}{R} = \frac{1}{\omega_0 RC}$$
where \(R\) is the total loss resistance (ohmic, dielectric, discharge).
Quality factor \(Q\) determines how long energy is retained in the regime (one convenient representation for energy decay is):
$$E(t) = E_0 \exp\left(-\frac{\omega_0 t}{Q_\mathrm{eff}}\right)$$
where \(Q_\mathrm{eff}\) denotes an effective quality factor defined for energy decay in the chosen model and boundary definition.
Key point: high quality factor means that for the same level of circulating energy \(A\), the required compensation becomes smaller.
This is not a violation of energy conservation, but its long circulation in fields rather than immediate consumption.
3.2 Gas Discharge as a Controlled Nonlinear Element
The central feature of VENDOR is the use of gas discharge (air or inert gas in the active node) not as an energy source, but as a dynamic nonlinear conductivity element.
Townsend Avalanche
With sufficient electric field \(E\), a free electron in gas, accelerating, ionizes a molecule, creating an additional electron:
$$n_e(x) = n_{e,0} \exp(\alpha x)$$
where:
\(n_e\) — electron concentration
\(\alpha\) — first Townsend coefficient (depends on \(E\) and gas type)
\(x\) — distance traveled by electron
Important: this is not an energy source, but a mechanism for a sharp change in conductivity \(\sigma(E,t)\).
The energy of the ionization process is taken from the electric field created by the VENDOR circuit, not from “air”.
Corona Discharge
With certain electrode geometry, a region of weakly ionized plasma (corona) emerges, which has:
Nonlinear I–V characteristic: conductivity depends nonlinearly on field
Pulsed structure: corona emits current pulses enriched in higher harmonics
Phase sensitivity: corona can either stabilize or destroy the resonant regime depending on phase
From an engineering standpoint, corona can act as a fast nonlinear conduction gate, allowing the system to adapt to changes in load and conditions.
Streamer Transitions
When certain conditions are exceeded, corona can transition to streamer mode — formation of conducting plasma “filaments” that:
Sharply change instantaneous conductivity and loss structure
Alter pulsed current waveform
Are controlled in VENDOR by architecture and control to prevent regime destruction
3.3 Self-Oscillating Regime and Limit Cycle
In nonlinear systems with feedback and constraints, a stable periodic trajectory in phase space emerges — a limit cycle:
$$\dot{x}_1 = f(x_1, x_2)$$
$$\dot{x}_2 = g(x_1, x_2)$$
where functions \(f, g\) contain nonlinear terms (discharge dependence, geometric constraints).
Properties of limit cycle:
Oscillation amplitude is independent of initial conditions (unlike a linear resonator)
Stability is formed by nonlinearities that limit growth
External perturbations are weakened by natural stabilization
In VENDOR, this means: the regime arrives at a stable state with predictable amplitude and spectrum, independent of small input variations.
3.4 Multi-Channel Discharge Structure as Stability Factor
VENDOR uses several discharge channels or elements with overlapping activation conditions. This provides:
Adaptation to drifts: if one channel loses optimality (electrode erosion, humidity change), another “takes over” the regime
Smoothing of spectral gaps: multi-channel design fills “dead zones” in input signal spectrum
Engineering reliability: regime can be maintained even with local failures
Analogy: just as a multi-nozzle injection system in an ICE ensures mixture formation stability, multi-channel discharge ensures electrodynamic regime stability.
4. Two-Circuit Architecture: Separation of Functions
4.1 Circuit A: Regime Formation and Maintenance
Circuit A (Active Core) is responsible for:
Formation of nonlinear electrodynamic regime with high internal circulation \(A(t)\)
Maintaining regime amplitude within stability limits
Compensating maintenance losses \(B_{\text{maint}}(t)\) through external input
Circuit functions:
Pulsed pumping: delivering short energy pulses to resonant structure
Discharge control: controlling gas discharge regime to optimize losses
Stability protection: preventing exit from the stable operating region
4.2 Circuit B: Power Extraction Through Classical Induction
Circuit B (Linear Extraction) operates according to laws of classical electromagnetic induction:
$$\mathcal{E} = -\frac{d\Phi_B}{dt} = -\frac{d}{dt}\left(\int \vec{B} \cdot d\vec{A}\right)$$
Variable magnetic flux from the active regime induces EMF in an extraction winding. This EMF is converted to useful power through:
Rectification (diode bridge)
Stabilization (capacitor filter)
Inversion (conversion to standard load power parameters)
Lenz’s Law and Back-Action:
Any power extraction creates a loaded quality factor \(Q_L\), reducing total quality factor:
$$\frac{1}{Q_{\text{total}}} = \frac{1}{Q_{\text{core}}} + \frac{1}{Q_L}$$
This means extraction always increases losses \(B(t)\) and the required compensation:
$$B_{\text{new}} = B_{\text{old}} + \Delta B_{\text{load}}$$
However, circuit separation allows architectural and phase management of this back-action, minimizing regime disruption until reaching the physical stability limit.
4.3 Architectural Isolation and Its Significance
In classical generators, load directly affects the source (mechanical shaft, excitation), causing immediate braking by Lenz’s law.
In VENDOR, the extraction circuit is functionally isolated from the regime formation circuit:
Energy extraction does not instantly destroy the regime formation mechanism
Regime can adapt and reconfigure within its stability region
Control can provide “soft” interaction between circuits
This does not mean the regime cannot be destabilized by excessive load; rather, the architecture is designed so that load influence is managed and the loss of stability occurs predictably, not as an immediate mechanical braking effect.
This is not a cancellation of Lenz’s law (which always applies), but its engineering optimization.
5. Control Systems and Buffer (BMS)
5.1 Role of Energy Storage
The buffer battery in VENDOR performs several functions:
Transient compensation: during load spikes (motor starting currents, pulse loads) the battery can briefly provide additional power
DC bus voltage stabilization: preventing voltage sags during dynamic loads
Control system power: control electronics require a stable and protected source
Energy recuperation: in reduced load modes, part of the extracted energy can be directed to the buffer
Critically important: the battery is NOT a “hidden energy source”. It is a buffer whose energy comes from the VENDOR system itself, and energy withdrawal from the buffer is reflected in the energy balance as an additional load on the regime circuit.
5.2 BMS and Stability Management
BMS (Battery & Mode Management System) controls:
Battery operation mode: charge, discharge, overcharge and deep-discharge protection
Transient processes: soft start, dI/dt limitation during load switching
Regime protection: preventing sharp voltage drops that can destroy the electrodynamic regime
BMS is not simply an electronic switch, but a regime stability control system, because a nonlinear electrodynamic regime is sensitive to dynamic disturbances and requires active management.
6. Parametric Excitation and Energy Amplification
6.1 Parametric Resonance in RLC Circuits
In circuits with variable parameters (e.g., \(L(t)\) or \(C(t)\)), parametric resonance is possible, where energy can be transferred from a control signal to an oscillatory regime with enhanced effectiveness:
$$\frac{d^2q}{dt^2} + 2\gamma\frac{dq}{dt} + \omega_0^2(1 + \mu(t))q = 0$$
where \(\mu(t)\) is temporal parameter modulation (e.g., \(\mu(t) = \mu_0 \cos(2\omega_0 t)\) for parametric excitation at the second harmonic).
Under certain conditions, oscillation energy grows exponentially until reaching nonlinear limitation, producing amplification without violating energy conservation.
Physics: energy is taken from the control signal but transferred into the oscillatory regime more effectively than by direct excitation.
6.2 Regime Amplification vs. Energy Creation
Critical clarification:
“Amplification” of regime means: acceleration of energy circulation, increase in field intensity, and regime stabilization with less energy loss per cycle.
This does NOT mean: energy creation from nothing.
In VENDOR, energy is amplified (in the sense of accumulation in fields) through proper pulse synchronization and nonlinearity control, but total system energy never exceeds the sum of external input plus initial conditions minus losses.
System Boundary: Why “η > 100%” Appears
The “efficiency paradox” is almost always a boundary-definition error: measuring only the control/maintenance channel while ignoring other inputs and stored-energy changes.
WRONG boundary (common mistake)
────────────────────────────────────────────────────────────────
AC/DC supply ──► [ P_control ] ──► Active Core + Extraction ──► P_out
(only this is counted as input)
(ignored: additional inputs, storage change, reflected load losses)
Right boundary (correct energy audit)
────────────────────────────────────────────────────────────────
All electrical inputs ───────────────► ┌──────────────────────────────┐
│ SYSTEM BOUNDARY │
│ Active Core + Extraction │
│ + Buffer + Control │
└──────────────────────────────┘
measured as P_in,total ───────────► P_out + B_total + dE/dt
Correct accounting uses total measured input at the system boundary, includes all irreversible losses, and tracks stored-energy change.
7. Why Linear Efficiency Gives “Implausible” Results
7.1 System Boundary Error
If one incorrectly defines efficiency using only the regime-maintenance channel, e.g.:
$$\eta_{\text{apparent}} = \frac{P_{\text{out}}}{P_{\text{control}}}$$
then \(\eta_{\text{apparent}}\) can appear >>100%. This is not a physical efficiency; it is a boundary-definition artifact.
If \(P_{\text{out}}\) is significant and \(P_{\text{control}}\) is small (due to high quality factor and effective control), the ratio becomes misleading.
This is not a contradiction but a model error.
7.2 Worked Example: Correct vs. Incorrect Efficiency
Consider a steady-state operating point with the following measured quantities (system boundary includes all electrical inputs):
Total electrical input: \(P_{\text{in,total}} = 2000\,\text{W}\)
Total irreversible losses at boundary: \(B_{\text{total}} = 1500\,\text{W}\)
Energy balance check:
$$P_{\text{in,total}} = P_{\text{out}} + B_{\text{total}} + \frac{dE_{\text{stored}}}{dt}$$
$$2000 = 400 + 1500 + 100 \quad \checkmark$$
Incorrect (“apparent”) efficiency occurs when someone measures only the maintenance/control channel, e.g. \(P_{\text{control}} = 200\,\text{W}\):
$$\eta_{\text{apparent}} = \frac{P_{\text{out}}}{P_{\text{control}}} = \frac{400}{200} = 2.0 \;\; (200\%)$$
This is a boundary error: \(P_{\text{control}}\) is not the total input; it is only the subset used to sustain the regime.
Correct efficiency uses total measured input at the system boundary:
$$\eta_{\text{true}} = \frac{P_{\text{out}}}{P_{\text{in,total}}} = \frac{400}{2000} = 0.20 \;\; (20\%)$$
Interpretation: the system is not “creating energy.” The apparent paradox appears only when input power is undercounted or when stored-energy change is ignored.
8. Role of Medium (Air, Gas) in Circuit A
8.1 Medium as Boundary Condition, Not Energy Source
The medium performs three roles:
Reactive reservoir: air has dielectric permittivity \(\varepsilon_r \approx 1\) and can support electrostatic and magnetic fields
Loss channel: ionization, molecular excitation, ozone synthesis and other phenomena consume energy from the regime
Stability conditions: humidity, pressure, and air composition determine discharge onset thresholds and oscillation spectrum
The medium is NOT an energy source. It determines how the system works but does not power it.
Analogy: water is not an energy source in a hydroturbine, but water presence determines whether the system can operate. Without water there is no regime, but water itself does not generate energy.
8.2 Mechanistic Hypotheses Consistent with Classical Electrodynamics
The medium (air or inert gas) is treated as a working medium and boundary condition for a nonlinear electrodynamic regime.
Its exact contribution to regime dynamics is an active research topic, but several concrete mechanisms are consistent with classical physics and known gas-discharge behavior:
H1 — Nonlinear impedance modulation (fast conductivity gating):
discharge dynamics produce rapid, field-dependent changes in effective conductivity \(\sigma(E,t)\) and loss resistance \(R(t)\),
enabling efficient transfer of energy from pulsed pumping into the resonant state (mode shaping, phase-locked gating).
H2 — Effective capacitance/permittivity modulation (quasi-parametric interaction):
space-charge formation, ion density, and local field redistribution can modulate the effective capacitance/permittivity of the active region,
producing a parametric-like contribution to regime amplification under synchronized pumping (without introducing any nonconservative energy source).
H3 — Spectrum enrichment and mode-selection via discharge microstructure:
corona/streamer micro-pulses generate higher-harmonic content and non-sinusoidal waveforms that can couple into specific resonant modes,
improving regime selectivity and stability (while also introducing measurable loss channels).
Importantly, these hypotheses describe how the medium shapes regime formation and stability, not how it supplies net energy.
Any contribution of the medium is accounted for through measurable changes in losses, stored energy, and boundary-defined input/output flows.
9. Verification and Measurability
9.1 Energy Audit
Any claim about a VENDOR system must be supported by a complete energy audit:
$$\text{energy}_{\text{total input}} = \text{energy}_{\text{losses}} + \text{energy}_{\text{output}} + \Delta\text{energy}_{\text{storage}}$$
where:
Left side — total energy introduced into the system through all input channels
Losses — measured through heat generation, radiation, ozone synthesis, etc.
Output — active power available at output for the load
Storage — change in energy in buffer and active circuit fields
Such an audit should be conducted with ±5–10% accuracy and across multiple load regimes.
9.2 Spectral Analysis and Regime Stability
A regime-based system is characterized by:
Spectral composition: FFT of voltage/current signals should show a structured spectrum with a dominant resonant frequency
Amplitude stability: at fixed load, regime oscillation amplitude should be stable within ±5%
Response speed: regime recovery time after a load spike should be <100 ms
These indicators are measured with an oscilloscope and a spectrum analyzer.
9.3 Stability Boundaries and Physical Limits
When exceeding permissible extraction, the regime should:
Degrade smoothly (amplitude reduction)
Or stabilize at a new level
Or completely shut down
This is expected physical behavior, not “magical system failure”.
10. Comparison with Classical Systems
Aspect
Classical Generator
VENDOR (Regime-Based System)
Power output mechanism
Mechanical shaft, excitation (direct)
Induction through isolated circuit
Load action on source
Immediate braking (Lenz’s law)
Controlled influence with architectural protection
Required energy input
Directly proportional to output
Proportional to losses, nonlinearly dependent on load
Oscillation amplitude
Depends on initial conditions (linear)
Independent (limit cycle, nonlinearity)
Adaptation to disturbances
Requires external control
Built into architecture (self-oscillations)
Output spectrum
Determined by mechanics (60 Hz or 50 Hz)
High-frequency, modulatable
Losses in regime formation
Minimal (ideal flywheel rotation)
Significant (discharge, radiation), but controllable
11. Limitations and Open Questions
11.1 Fundamental Questions
Field interaction mechanism with air molecules: the exact role of ionization and molecular excitation in the energy balance requires detailed analysis at the level of molecular physics and spectroscopy.
Mathematical description of parametric resonance in a system with gas discharge: classical parametric resonance theory assumes smooth parameters; including nonlinear discharge requires theory expansion.
Minimum losses and maximum efficiency: is there a fundamental limit for quality factor in discharge regimes? How to optimize the compromise between stability and losses?
VENDOR.Energy™ architecture represents a legitimate class of electrodynamic systems based on classical physics and distinct from traditional generators by its separation of regime formation, loss compensation, and power extraction functions.
Incorrect application of linear energy models to regime-based systems leads to an apparent violation of principles (efficiency >100%), but this is a model error, not a physics violation.
Key scientific results:
Canonical A–B–C model provides a correct energy-balance framing for regime-based systems
Gas discharge functions as a controlled nonlinear element, not an energy source
Parametric resonance explains regime amplification without violating energy conservation
Architectural circuit isolation allows minimizing back-action during power extraction
Control system (BMS) is critical for maintaining nonlinear regime stability
VENDOR systems require further scientific verification, especially regarding precise determination of gas-medium role and a deeper fundamental explanation of parametric processes, but the current level of engineering validation and patent protection supports continued R&D.
Technology Readiness Level (TRL): 5–6 (successful demonstration in a relevant environment; path to commercialization requires solving scaling and measurement standardization).
References
Maxwell J. C. “A Treatise on Electricity and Magnetism”. Classical electrodynamics, foundation of circuit B description. https://archive.org/details/treatiseelectric — Basic EM theory.
Losses in electrodynamic systems: Griffiths D. J. “Introduction to Electrodynamics” (4th ed.). — Ohmic losses, dielectric losses and radiation in classical electrodynamics.
Khalil, H. K. Nonlinear Systems. 3rd ed., Prentice Hall. — Foundational methods for stability, Lyapunov analysis, and nonlinear control (relevant to regime stability management).
Slotine, J.-J. E., & Li, W. Applied Nonlinear Control. Prentice Hall. — Practical nonlinear control frameworks applicable to mode stabilization and disturbance rejection.
Åström, K. J., & Murray, R. M. Feedback Systems: An Introduction for Scientists and Engineers. Princeton University Press. — Control fundamentals and feedback interpretation for energy systems with internal states.
Assuming output is “maintained” by \(P_{\text{control}}\) directly
\(\frac{dE_{\text{stored}}}{dt}\)
Stored-energy change in buffer + fields (positive when charging/accumulating)
\(P_{\text{in,total}} = P_{\text{out}} + B + \frac{dE}{dt}\)
Ignoring buffer charging/discharging when interpreting measurements
Appendix: Symbols and Notation
Symbol
Meaning
Unit
\(P_{\text{in}}, P_{\text{out}}\)
Input / output power
W
\(\eta\)
Efficiency
—
\(R(t)\)
Operational regime state
—
\(A(t)\)
Internal energy turnover
J
\(B(t)\)
Irreversible regime losses
W
\(P_{\text{control}}\)
External loss-compensation power
W
\(E_{\text{total}}\)
Total system energy
J
\(L\), \(C\)
Inductance, capacitance
H, F
\(Q\)
Resonator quality factor
—
\(\omega_0\)
Resonant angular frequency
rad/s
\(\alpha\)
First Townsend coefficient
m⁻¹
\(E\)
Electric field strength
V/m
\(\sigma\)
Medium conductivity
S/m
\(\Phi_B\)
Magnetic flux
Wb
\(\mathcal{E}\)
Electromotive force (EMF)
V
\(n_e\)
Electron concentration
m⁻³
\(\Delta E_{\text{stored}}\)
Change in stored energy
J
Disclosure Note: Modeling Scope vs. Implementation Scope
This article intentionally presents a mathematical and boundary-correct formulation of energy balance for regime-based electrodynamic systems.
Its purpose is to eliminate common interpretation errors (especially the “η > 100%” paradox caused by incorrect system boundaries),
not to disclose the full implementation details of VENDOR.Energy™ hardware.
The numerical examples and balance equations in this paper are therefore conservative, model-level illustrations.
They show how to account for total measured input, irreversible losses, and stored-energy change—but they do not encode
the proprietary engineering decisions that govern real-world power scaling.
Why this matters:
A reader may look at a worked example (e.g., hundreds of watts) and incorrectly assume it represents the system’s maximum capability.
In reality, power is a function of configuration (architecture, regime stability margins, extraction design, control strategy, thermal/safety constraints),
and those implementation parameters are not published here.
Certain engineering solutions that enable higher-output regimes are treated as protected know-how (and in parts as patent-described embodiments),
and are disclosed only through controlled documentation to qualified parties.
Accordingly, this publication should be read as a correct scientific framing—a way to evaluate measurements without falling into linear-model traps—
while the detailed implementation, validation methodology, and configuration-dependent performance envelopes are handled separately within the project’s
controlled documentation (available via the Silent Pitch Room).
In short: the math here explains how to measure and interpret an open nonlinear regime correctly.
It does not attempt to publish the full set of engineering methods used to reach higher-power operating regimes.
Manage Consent
To provide the best experiences, we use technologies like cookies to store and/or access device information. Consenting to these technologies will allow us to process data such as browsing behavior or unique IDs on this site. Not consenting or withdrawing consent, may adversely affect certain features and functions.
Functional
Always active
The technical storage or access is strictly necessary for the legitimate purpose of enabling the use of a specific service explicitly requested by the subscriber or user, or for the sole purpose of carrying out the transmission of a communication over an electronic communications network.
Preferences
The technical storage or access is necessary for the legitimate purpose of storing preferences that are not requested by the subscriber or user.
Statistics
The technical storage or access that is used exclusively for statistical purposes.The technical storage or access that is used exclusively for anonymous statistical purposes. Without a subpoena, voluntary compliance on the part of your Internet Service Provider, or additional records from a third party, information stored or retrieved for this purpose alone cannot usually be used to identify you.
Marketing
The technical storage or access is required to create user profiles to send advertising, or to track the user on a website or across several websites for similar marketing purposes.